AIR HANDLING UNITS

Frames of boxes for units, made of aluminium profiles with skewed corners, come in three sizes, – depending on the type of environment (exterior, interior, hygienic). The edges of the profiles are connected with aluminium or plastic angles which are highly resistant to mechanical stress and climatic conditions. Sandwich panels are then fitted into the frame.


The efficiency of electric motors used in air handling units complies with ErP standard for fans (EU directive, no. 427/2011).


Interior, exterior and hygienic panel design

Parameters acc. to EN 1886

Interior design – panel thickness 25mm

Mechanical stability D1
Air leakage factor L2
Thermal insulation T3
Thermal bridging factor TB2
Acoustic insulation 32dB
Filter bypass leakage F9

Exterior design – panel thickness 45mm

Mechanical stability D1
Air leakage factor L2
Thermal insulation T2
Thermal bridging factor TB2
Acoustic insulation 34dB
Filter bypass leakage F9

Hygienic design – panel thickness 40mm

Mechanical stability D1
Air leakage factor L2
Thermal insulation T2
Thermal bridging factor TB2
Acoustic insulation 34dB
Filter bypass leakage F9

Air Handling Unit Portfolio

AIR FLA

AIR FLA Unit

This unit, with a flat design, is used for installation under a ceiling or within the ceiling construction itself.

Components of basic model:

  • Outside air filter, filtration class EU4 (optionally up to EU9)
  • Hot water coil with copper pipes fitted with aluminium lamellas stamped onto the pipe
  • Radial ventilator

Optional components:

  • Electric heater protected with operational and emergency thermo contact
  • Direct evaporative cooler or chilled water coil from copper pipes fitted with aluminium lamellas stamped onto the pipe
  • Microprocessor measurement and control of all regulation and protection functions, optionally with remote control
  • Differential pressure sensors monitoring the condition of filters’

Design: interior
Mounting: ceiling, floor, wall
Air flow: 500 – 5000 m3.h-1
Sizes: 01.00, 02.00, 03.50, 05.00

AIR COM

AIR COM Unit

The unit is designed as compact unit.

Components of basic model:

  • Outside and exhaust air filters, filtration class EU4 (optionally up to EU9)
  • Cross-flow heat exchanger fitted with aluminium lamellas
  • Hot water coil with copper pipes fitted with aluminium lamellas stamped onto the pipe
  • Two independently controlled radial fans

Optional components:

  • Electric duct heater protected with operational and emergency thermo contact
  • Direct evaporative cooler or chilled water coil from copper pipes fitted with aluminium lamellas stamped onto the pipe
  • Bypass with actuator driven dampers
  • Mixing chamber with actuator driven dampers
  • Microprocessor measurement and control of all regulation and protection functions, optionally with remote control
  • Differential pressure sensors monitoring the condition of filters’

Design: interior, exterior
Mounting: ceiling, floor, wall
Air flow: 1000 – 8000 m3.h-1
Sizes: 02.00, 03.00, 04.00, 05.00, 06.00, 07.00

AIR COM DEC

AIR COM DEC Unit

This unit designed as flat, ceiling mounted, and is used for installation under a ceiling or within the ceiling construction itself.

Components of basic model:

  • Outside and exhaust air filters, filtration class EU4 (optionally up to EU7)
  • Heater protected with operational and emergency thermo contact
  • Fans driven by EC motors with maximum efficiency in its class
  • Outside and exhaust air dampers automatically controlled by actuators
  • Connection terminals
  • Highly efficient cross-flow heat exchanger

Optional components:

  • Hot water coil with copper pipes fitted with aluminium lamellas stamped onto the pipe or electric duct heater
  • Direct evaporative cooler or chilled water coil from copper pipes fitted with aluminium lamellas stamped onto the pipe
  • Bypass with actuator driven dampers
  • Microprocessor measurement and control of all regulation and protection functions, optionally with remote control
  • Differential pressure sensors monitoring the condition of filters’

Design: interior
Mounting: ceiling, floor, wall
Air flow: 300 – 1000 m3.h-1>
Sizes: 00.30, 00.50, 00.80, 01.00

AIR INO, INE

AIR INO, INE Unit

The unit is composed of individual functional chambers which are assembled according to project requirements.

Design: interior, exterior
Mounting: intake and exhaust above each other or side by side
Air flow: 1000 – 90,000 m3.h-1
Sizes: 03.15, 05.00, 08.00, 10.00, 14.00, 18.00, 22.50, 28.00, 31.50, 40.00, 45.00, 50.00, 56.00, 63.00, 71.00, 80.00

Air Flow

Air Flow Performance of Units

Air flow [3.h-1] – air velocity in a unit up to 2,9 m.s--1

  • models with filters, heaters or coolers
  • models with a standalone fan

CONTACT

Tel.: +420 519 500 811
E-mail: obchod.vyroba@azklima.com